MAKING
A
This is a building carefully
conceived, thoughtfully
delivered and built to
stand the test of time.
DIFFERENCE
Floor to ceiling
Levels 01 - 05 - 2,750mm
(2,650mm core and perimeter areas)
Level 06 - 2,520 mm
RAISED FLOOR
150mm nominal
Cycle spaces
Total 58, including 4 Sheffield stands,
14 Brompton lockers
Showers
6 showers, 1 AWC shower
Total lockers
76
PASSENGER LIFTS
3 x 1,000kg / 13 persons @ 1.6m/s
AIR CONDITIONING
CHW generated by x3 reversible heat pumps
located in external Level 04 plantroom.
Primary and secondary distribution
pumps are located within the basement air
handling unit plantroom. Space provided
for ancillary tenant cooling adjacent to
heat pumps in L04 plantroom. Cooling
generally delivered by fan coil units to
office floorplates
MECHANICAL OCCUPANCY DENSITY DESIGN
1 person/8 sq m (allowing for 20% absenteeism)
SMALL POWER
6W/m²
GENERATOR BACKUP POWER
Emergency power is provided by a 50kVA
life safety generator in the roof plantroom.
It provides secondary supply to fire fighting
lobby smoke control, fire fighting lift and
car park extract only
LIGHTING
4.5W/m² Cat A, 1.5W/m² Cat B allowance.
Back of house has LED lighting throughout
with centralised lighting control system.
Front of house features all LED lighting
FIRE ALARM
Open protocol fully addressable fire alarm
system with dedicated loops
for each
tenancy using Apollo XP95 devices.
BS 5839-1 Category L1
SECURITY/ACCESS
Landlord access control provided to
entrance doors for out-of-hours use.
Landlord access control to shared amenity
areas. Lift access is via a
landlord-provided
destination control system
CCTV
External cameras monitoring façade.
CCTV coverage at internal entrances and at
designated fire escapes. CCTV at primary
access points, reception desk, lift lobby at
ground floor, and within lifts
BMS
Building Management System that monitors and controls all base build plant
MEANS OF ESCAPE
1 person / 6 sq m